KEPA-1000 Portable Substation Preventive Diagnostic Gas Analyzer
Substation (GIS/GIT) Gas Analyzers

KEPA-1000

Portable Substation Preventive Diagnostic Gas Analyzer

Model
KEPA-1000
Manufacturer
SENSORONIC
Category
Gas Analyzers › Substation (GIS/GIT) Gas Analyzers

Parameters: H2O, SF6, SO2, CO, CO2, Pabs, Pdif, Tamb, Flow

IndustriesPower Utilities

Overview

KEPA-1000 is a portable direct-reading preventive diagnosis analyzer that assesses the condition of gas-insulated transformers (GIT) and gas-insulated switchgear (GIS) in service. It measures and analyzes insulation decomposition gases and SF6 decomposition gases on site and immediately produces a diagnosis.

It simultaneously measures SF6 purity, moisture, SO2, CO, CO2 and breaker pressure; a patented algorithm removes CO interference on SO2 and compensates for temperature and pressure effects on each sensor. By combining analysis data with an accumulated database, it automatically identifies fault types such as partial discharge, overheating/degradation and internal discharge.

It includes an MFC for automatic sample flow control, pump-back re-injection and gas recovery, an 8-inch color touch screen and a 24-column mini printer.

Key Features

  • Simultaneous measurement of SF6 purity, moisture, SO2, CO, CO2, insulation decomposition gases and breaker pressure
  • Two modes: gas-insulated transformer (GIT) and gas-insulated switchgear (GIS)
  • Preventive diagnosis solution with a patented algorithm
  • CO interference on SO2 is removed and applied to the diagnosis algorithm
  • Temperature and pressure interference compensation for each sensor
  • Immediate on-site analysis and diagnosis of insulation decomposition gases from GIT and GIS
  • On-site condition diagnosis combining analysis data with the accumulated database
  • Insulation decomposition gases from partial discharge, overheating/degradation and internal discharge
  • and automatic identification of the cause (fault type) of abnormal SF6 decomposition gas
  • Modular sensor design for easy calibration and maintenance
  • Review of measurement data and results, with output to the built-in 24-column mini printer
  • MFC for automatic sample gas flow control
  • Pump-back re-injection of the sample gas used for measurement
  • Used gas can be stored in a recovery device (Tedlar bag)
  • Digital storage and review of analysis data to build a database
  • 8-inch color TFT-LCD with interactive touch-screen user interface

Measured Parameters

ParameterMeasuring Range
H₂O-60℃~+20℃
SF₆0~100%vol
SO₂0~10ppmvol
CO0~1,000ppmvol
CO₂0~5,000ppmvol
Pabs0~10Bar
Pdif-600~120mBar
Tamb-40℃~125℃
Flow350~1,000sccm
Temperature0-125C
Humidity0-100%

Measurement Performance

ParameterMethod · Accuracy · Resolution
H₂OMethod: Polymer · Accuracy: ±2℃ · Resolution: 0.1
SF₆Method: NDIR · Accuracy: <±0.5FS · Resolution: 0.1
SO₂Method: UV-DOAS · Accuracy: <±1%FS · Resolution: 0.1
COMethod: Electrochemical · Accuracy: <±2%FS · Resolution: 1
CO₂Method: NDIR · Accuracy: <±30 · Resolution: 1
PabsMethod: Mass Flow · Accuracy: ±1.5%FS · Resolution: 0.1
PdifMethod: Mass Flow · Accuracy: ±0.5%FS · Resolution: 1
TambMethod: Capacittance · Accuracy: ±0.2℃ · Resolution: 0.1
FlowMethod: MFC (for SF₆) · Accuracy: <±2% · Resolution: 1

Specifications

ManufacturerSENSORONIC
DisplayLCD : 8inch TFT-Color LCD / 800X480 pixel / Illuminance : 500cd/㎥ / Touch screen
Warm-up5Minute
Memory64GB
Data backupUSB
ConnectionQuick Coupling with 2.5m Flexible Tube
Mass Time setup3, 5, 8, 10Minutes User’s setup
Sample Flow setup350sccm, 700sccm, 1,000sccm Selectable
Printer24Column Thermal Printer
Recovery Pressure30Bar(Max)
Purge600cc/min (Vacuum pump)
Power consumption80VA
Dimensions375mm(W) X 220mm(H) X 245mm(D)
Power supplyLithium-ion Rechargeable Battery 12V/18A
Weight11kg
OptionsRecovery system (pump back) / pressure: 30 bar

Applications

  • Gas-insulated switchgear
  • Transformer