Parameters: CO
IndustriesBuilding & HVAC
Measurement PrincipleElectrochemical
Overview
JM-AM4302R is a battery-powered electrochemical CO alarm with relay output, graded alarms at 50, 100 and 300 ppm up to 85 dB, resistance to acetic acid and ethanol, self-test and silence buttons and a 10-year life, compliant with UL2034, EN50291 and RoHS.
Key Features
- Electrochemical technology
- Integrated with self-developed electrochemical CO sensor
- High selectivity, resistant to acetic acid and ethanol interference
- High detection accuracy over the full temperature and measurement range
- Fast response to elevated CO concentrations
- Audible and visual alarm with sound output up to 85 dB under graded alarm thresholds
- Relay signal output available for external control
- Self-checking and silence button functions
- Battery-operated with up to 10 years & nbsp; lifetime
- Compact design for easy installation
- Compliant with UL2034, EN50291, and RoHS
- OEM/ODM turnkey solutions available
Measured Parameters
| Parameter | Measuring Range |
|---|---|
| CO | 0~500 ppm |
Specifications
| Detection Gas | Carbon Monoxide |
|---|---|
| Working Principle | Electrochemical |
| Detection Range | 0-500ppm |
| Detection Accuracy | ±5ppm or ±5%@23C2C, take whichever is greater |
| Alarm Threshold | 50PPM Between 60 to 90 minutes / 100ppM Between 10 to 40 minutes / 300ppM Less than 3 minutes |
| Alarm Reset | Automatic reset when the leaked gas is cleared / Press the button to silence the sound |
| Working Conditions | -10C~+50C; 0%RH- 95%RH non condensing |
| Working Air Pressure | 86kPa -106kPa |
| Applicable Place | Indoor |
| Power Supply | Battery powered |
| Product Weight | Around 600g |
| Product Size | 130*58*80mm |
Applications
- Indoor CO leak detection
- Residential and commercial CO alarms
Related Products

Fixed Gas Detectors & Alarms
JT-AM5301
NDIR CH₄ Gas Detector with Visual, Audible and App Alarms
Parameters: CH4

Fixed Gas Detectors & Alarms
JT-AM5301-EV
NDIR Four-Channel Methane Alarm
Parameters: CH4

Fixed Gas Detectors & Alarms
JT-AM5301-JG
Residential TDLAS Natural Gas Alarm
Parameters: CH4

Fixed Gas Detectors & Alarms
AM4301
Combined CO & CH₄ Gas Alarm
Parameters: CH4, CO