Parameters: R32, R290, R410A, R134a, R454A, R454B, R454C, R1234ze, R1234yf
Measurement PrincipleNDIR
Overview
AM4209 is a portable NDIR refrigerant leak detector for HFCs, HFOs and blends such as R32, R290, R410A, R134a, R454A/B/C and R1234ze/yf, detecting static leaks down to 1 g/year and dynamic leaks to 3 g/year with sub-second response. A large ppm/bar-graph display, tip alarms and a 10-hour Type-C battery suit HVAC service and manufacturing.
Key Features
- Non-Dispersive Infrared (NDIR) technology
- Highly sensitive leak detection of HFCs, HFOs, and blends of refrigerants
- Built-in self-developed NDIR refrigerant gas sensors
- OEM & ODM design capability
- Real-time ppm and bar graph working mode for fast the leakage area localization
- Long lifespan of 10 years
- Built-in lithium battery with large capacity to support fast charging
Measured Parameters
| Parameter | Measuring Range |
|---|---|
| R32 | To be confirmed |
| R290 | To be confirmed |
| R410A | To be confirmed |
| R134a | To be confirmed |
| R454A | To be confirmed |
| R454B | To be confirmed |
| R454C | To be confirmed |
| R1234ze | To be confirmed |
| R1234yf | To be confirmed |
Specifications
| Refrigerant Gas | R32/R290/R410A/R134a/R454A/R454B/R454C/R1234ze/R1234yf |
|---|---|
| Maximum sensitivity | Static: 0.03oz/a (1g/a); motion: 0.1oz/a (3g/a) |
| Response time | <1s (typical) |
| Working environment | 0℃~40℃ (32℉~104℉), <75%RH (non-condensing) |
| Storage environment | 20℃~60℃ (-4℉~140℉); <80%RH |
| Charging time/standby time | 6H/10H (backlight off) |
| Automatic shutdown | 10 min |
| Protection level | IP54 |
| Display | LED, LCD, buzzer |
| Compliance | LCD color screen |
| Power supply | Lithium-ion: 3.7VDC, 2550mAh (unchangeable) |
| Lifetime | rechargeable |
Applications
- HVAC servicing
- Equipment manufacturing
- Maintenance and safety inspection