AM1008W Integrated Air Quality Sensor Module AM1008W
Industrial Sensors & Transmitters

AM1008W

Integrated Air Quality Sensor Module AM1008W

Model
AM1008W
Category
Flow, Pressure & Process Instruments › Industrial Sensors & Transmitters

Parameters: CO2, PM, VOC, Temperature, Humidity

Overview

AM1008W is an ultra-thin 4-in-1 IAQ sensor module combining particle, auto-calibrating NDIR CO2, VOC and temperature/humidity sensing, outputting PM1.0, PM2.5 and PM10 over UART or I2C. It is EMC compliant and available for OEM/ODM customization.

Key Features

  • 4 in 1 sensor module which integrated particle, CO2, VOC and RH&T
  • PM1.0 PM2.5 and PM10 output simultaneously
  • Auto-calibration NDIR CO2 sensor
  • Precise accuracy and robust performance
  • With voltage regulator design and EMC compliant, strong anti-static ability
  • Ultra-thin structure

Measured Parameters

ParameterMeasuring Range
CO20~5000 ppm
PM0~1000 μg/m³
VOC0~3 level
Temperature-20~70 °C
Humidity0~95 %RH

Specifications

Measurement rangeCO2: 0~5000ppm; PM: 0~1000μg/m³; VOC: 0~3level;
Temperature-20℃~70℃; RH:0%~95%RH
PM accuracyPM2.5: 0~35μg/m³, ±5μg/m³ >35μg/m³, ±15% of reading (Condition: 0℃~40℃, 50±10%RH Reference instrument: TSI Dust Source: Cigarette + Arizona A1)
CO2 accuracy±(50ppm+5% of reading) (0~2000ppm, 0~50℃, 50±10%RH)
Working condition-10℃~50℃, 0~95%RH(non-condensing)
Storage condition-30℃~70℃, 0~95% RH(non-condensing)
Power supplyDC 5V±0.1V
Ripple wave<50mV
Working current<300mA
Signal outputUART_TTL
DimensionsW80*H50*D13.6(mm)

Applications

  • IAQ applications
  • Fresh air systems
  • Fresh air system controllers
  • Air quality monitors